87
|
Wed Mar 6 10:25:51 2024 |
VC | Fixed | Other | Other |
|
frequency linac | |
La frequence linac est passée à 2998.55MHz |
|
88
|
Tue Mar 19 16:24:36 2024 |
Entered by Vincent Chaumat from 134.158.76.115 on Tue Mar 19 16:24:21 2024 | Fixed | Info | Timing |
|
Synchro démontée | |
La synchro n'est plus en place à l'heure actuelle.
un générateur permet d'avoir des signaux en sortie du DEG1(modulateur) et du DEG4(Linac) (fréquence 10Hz)
|
|
89
|
Mon May 13 16:45:23 2024 |
Entered by Vincent Chaumat from 134.158.76.115 on Tue Mar 19 16:24:21 2024 | Fixed | Info | Timing |
|
RE: Synchro démontée | |
La synchro a été remise le 09/04/2024, le rapport et en P.J.
| Entered by Vincent Chaumat from 134.158.76.115 on Tue Mar 19 16:24:21 2024 wrote: |
|
La synchro n'est plus en place à l'heure actuelle.
un générateur permet d'avoir des signaux en sortie du DEG1(modulateur) et du DEG4(Linac) (fréquence 10Hz)
|
|
| Attachment 1: Rapport_synchro_marrs_2024.pdf
|
|
94
|
Mon May 27 16:35:09 2024 |
VC | Fixed | Fix | Timing |
|
Largeur impulsion Timing camera |
|
Les largeurs des impulsions de synchronisation de toutes les caméras de ThomX sont passées à 10µs (last value 5µs)
Camera linac TL1 TL2 TL3 EL DG spare et laser PC |
|
97
|
Thu Jun 27 16:33:16 2024 |
Entered by Vincent Chaumat from 134.158.76.115 on Thu Jun 27 16:33:02 2024 | Fixed | Info | Timing |
|
Synchro | |
Les codes synchros présent dans l'IHM phase et fréquence sont opérationnel (ancien code max 10Hz)
|
|
99
|
Tue Jul 16 11:07:39 2024 |
VC, ND | Fixed | Info | Timing |
|
Codes de synchro mis a jour (25Hz) | |
Les codes de synchro ont ete mis a jour et testes.
Il est maintannt possible de passer a 25Hz sur le linac et l'anneau. Les diags sont limites a 8,33Hz. |
|
100
|
Tue Jul 16 11:20:49 2024 |
VC, ND | Fixed | Info | Material |
|
Synthe linac | |
Le synthe du linac a ete remis en place et teste a bas niveau. |
|
101
|
Tue Jul 16 11:47:44 2024 |
VC, ND | Fixed | Info | Material |
|
RE: Synthe linac | |
Attention si vous passez pres de la baie 8: certains cables n'aiment pas etre caresse. Si le voyant trigger ne clignote plus, appelez la synchro...
| VC, ND wrote: |
|
Le synthe du linac a ete remis en place et teste a bas niveau.
|
|
|
102
|
Tue Jul 16 13:00:24 2024 |
VC, ND | Fixed | Info | Timing |
|
RE: Codes de synchro mis a jour (25Hz) | |
La limite sur les diags a levee. Ils peuvent passer a 25Hz aussi.
| VC, ND wrote: |
|
Les codes de synchro ont ete mis a jour et testes.
Il est maintannt possible de passer a 25Hz sur le linac et l'anneau. Les diags sont limites a 8,33Hz.
|
|
|
103
|
Thu Sep 12 09:23:09 2024 |
VC,ND | Fixed | Info | Timing |
|
Decalage temps de declenchement machine. | |
9:20 Le laser est a -8.20us
Verification du retard de la camera LI/OP/LAS.02 en decalant en temps le laser de 999us.
La camera se declenche bien environs 600us avant le laser.
Tests sous pylon: un retard de 500us avait ete mis manuellement dans la camera il est retire.
Maintenant la camera se declenche 120us avant le laser.
12:17 Decalage en temps de toutes la synchro. Maintenant le 0 est 200us avant la production des electrons.
Cela devrait etre transparent pour les utilisateurs.
Mise a jour du fichier de constantes de synchronisation.
Git pull.
Scan de verification avec le laser a -8.20us et le temps d'exposition de la camera a 100us. On voit bien le laser si le declenechement est entre -190us et -100us
Verification des parametres pylon des autres cameras. A priori il n'y a pas de retard caché.
Il faudra verifier en faisceau que tout va bien.
|
| Attachment 1: laser_scan_before.png
|
 |
| Attachment 2: camera_laser_scan_laser_at_999us_exp100us.png
|
 |
| Attachment 3: camera_laser_scan_laser_at_200us_exp90us_after_changing_edge.png
|
 |
| Attachment 4: camera_laser_scan_laser_at_m8us_exp100us_after_adjusting_timing.png
|
 |
|
104
|
Wed Dec 4 11:10:38 2024 |
VC | Fixed | Info | Timing |
|
procedure fréquence | |
dossier panneau\synchro (cdi)
./ring_frequency.py --help (voir le mode de fonctionnement)
./ring_frequency.py --freq "value" (choisi que des fréquences possible pour la div par 15)
./phase_shifter_rigol.py --phase "value" (attention change les phases de ch1 et ch2) |
|
105
|
Thu Dec 5 15:14:38 2024 |
VC | Fixed | Info | Tests |
|
MESURE STABILITÉ SYNCHRO | |
La synchronisation des signaux mesure suR le timing 50Hz
500MHz LI 500MHz RI => 18ps sdev
500MHz LI 50Hz => 190ps sdev
|
|
106
|
Fri Dec 20 12:03:29 2024 |
Entered by Nicolas Delerue from 134.158.195.142 on Fri Dec 20 12:03:15 2024 | Fixed | Fix | Timing |
|
Added a "diags only" button on Rep rate GUI | |
Two buttons have been added to the repetition rate interface (see attached screen shot):
- "diags only": Will inhibit all channels from the ring and linac delay generators
- "restore linac and ring": Will set all channels of the ring and linac delay generators to External triggering.
A git pull has been done. |
| Attachment 1: Screenshot_from_2024-12-20_12-03-09.png
|
 |
| Attachment 2: 20241220_115912.jpg
|
 |
| Attachment 3: 20241220_115919.jpg
|
 |
|
107
|
Thu Jan 9 14:12:45 2025 |
Entered by Nicolas Delerue from 134.158.195.144 on Thu Jan 9 14:12:31 2025 | Fixed | Info | Timing |
|
DS to monitor missed triggers | |
A ds to monitor missed triggers has been added in CALC/SY/missed_triggers
|
| Attachment 1: Screenshot_from_2025-01-09_14-24-06.png
|
 |
|
108
|
Wed Feb 19 10:59:16 2025 |
Entered by Super Team from 134.158.195.141 on Wed Feb 19 10:59:02 2025 | Fixed | Fix | Timing |
|
Carte synchro | |
Changement de carte synchro
le MCT2 de la carte en place à bruler
|
|
118
|
Fri May 16 11:12:32 2025 |
Entered by Vincent Chaumat from 134.158.76.115 on Fri May 16 11:12:17 2025 | Fixed | Info | Timing |
|
State of the art Synchro | |
Les performance de la synchro de ThomX au 16 mai 2025 sont:
Le jitter 500MHz Ring 500MHz Linac est de 8ps Sdev et 95% es événement dans 20ps 100 % dans 80ps (quelquesoit la fréquence de répétion) (Jitter rapide)
Le jitter entre les voies de synchro Linac et Ring est contenu dans 100ps (quelquesoit la fréquence de répétion) (jitter rapide)
La varition du temps entre les timing ring (drift timing) (quelquesoit la fréquence de répétion)
sont inférieurs à 3ns entre le modulateur et le linac
sont inférieurs à 1.5ns entre le modulateur et les diag
sont inférieurs à 200ps entre linac et ring (mesure plus précise avec jitter rapide)
|
| Attachment 1: jitter_rapide.png
|
 |
| Attachment 2: drift_timing.png
|
 |
|
119
|
Wed Jun 18 18:02:24 2025 |
Entered by Nicolas Delerue from 193.55.29.170 on Wed Jun 18 18:02:07 2025 | Fixed | Problem | Timing |
|
Etude des problèmes de déclenchement des générateurs de retard | |
La voie 19 du générateur de retard diags était déjà branchée sur le scope (ch1 - jaune)
Branchement de la voie 8 sur le scope (ch 2 vert).
Kicker d'injection sur ch3 (orange)
septum sur ch4 (violet)
Mode enveloppe pour voir si il y a des coups anormaux.
Image SCR_PA02: machine en standby: on ne voit rien.
Image SCR_PA03: on retire la longue durée d'impulsion sur la voie 8; toujours rien.
Allumage de la machine.
Imgae SCR_PA06: machine en trig, toujours pas de double déclenche.
Vérification sur les ICT: pas de double déclenche sur ICT1.
Conclusion: le problème n'est plus présent.
|
| Attachment 1: SCR_PA02.PNG
|
 |
| Attachment 2: SCR_PA03.PNG
|
 |
| Attachment 3: SCR_PA06.PNG
|
 |
|
131
|
Wed Aug 20 13:02:39 2025 |
VC RC | Fixed | Problem | Timing |
|
Redeclanche des DGs | |
scope (déclenche sur glitch inversé (inférieur à 50ns) CH1
CH1 trigext DeG4 (pris avec 1 "T" scope sur 1MOhm)
CH2 33MHz RI (in trigbox)
CH3 500MHz RI (in trigbox)
REF bruit
Septum à 0V de tension Kicker Inj & Ext "on" V nomimal
CH1-N4-CH2_33RI-CH3_500RI-V2.png
glitch présent sur CH1
Pas de bruit sur les signaux RI
=> si la tension cumulée des kickers (inj et ext) est supérieure à 11KV le glitch apparait :
CH1-N4-CH2_33RI-CH3_500RI-V3.png (limite de tension pour apparition du glitch)
=>le septum n'a aucun effet sur l'appartition du glitch
=>le cable de tri ext vers DeG3 diag n'a pas d'effet
=> Cable tranverse feedBack 500 et 16 débranché (IGLOO ELR2) pas d'effet
=> DeG2 (ring) déclenché par un géné pulse (12.5Hz non synchro de la machine) cable trig ext débranché coté Igloo
cable trig ext débranché coté D1 pas d'effet DeG 3 débranché
Defaut de comptage de la trigger box (plus de 12.5Hz ) tioujours des gliches
Les glitches venaient des bits de choix de fréquences de l'automate CA. certainement plus visible du au changement de programation de la CPLD (lecture des divisions en temps réél)
une ferrite sur la nappe qui véhicule les bits de choix (automate CA vers Trigger Box) resoud le probleme
|
| Attachment 1: CH1-N4-CH2_33RI-CH3_500RI-V2.png
|
 |
| Attachment 2: CH1-N4-CH2_33RI-CH3_500RI-V3.png
|
 |
|
132
|
Mon Sep 1 11:28:51 2025 |
VC | Fixed | Info | Timing |
|
réglage DEG4 --> DEG1 | |
Gen4, voie 1 => Gen1,voie2, RF Gun
Gen4, voie 2 => Gen1,voie3, Laser
Gen4, voie 6 => Gen1,voie4, RedPitaya
Gen4, voie 8 => Gen1,voie5, Salle de controle
Sauve en memoire 9 des DEG1 |
|
133
|
Mon Sep 1 16:46:34 2025 |
VC, ND | Fixed | Fix | Timing |
|
Recharge constante synchro 8 | |
Les constantes de synchronisation 8 (sans DEG 4) ont été rechargées. Toutes les valeurs sont remises à celles du 8 juillet 2025.
Les constantes de synchronisation 9 (avec DEG 4) ont été effacées. |