Entry   Entered by Super Team from 134.158.195.142 on Tue Nov 23 11:15:33 2021; IHM charge 
    Reply   Nicolas Delerue; RE: IHM charge 
       Reply   Nicolas Delerue; RE: RE: IHM charge 
          Reply   Nicolas Delerue; RE: RE: RE: IHM charge 
             Reply   Nicolas Delerue; RE: RE: RE: RE: IHM charge 
                Reply   Nicolas Delerue; RE: RE: RE: RE: RE: IHM charge 
                   Reply   Nicolas Delerue; RE: RE: RE: RE: RE: RE: IHM charge 
Message ID: 48     Entry time: Tue Nov 23 14:53:25 2021     In reply to: 47     Reply to this: 49
 Author: Nicolas Delerue 
 Status: New Solution 
 Type: Fix 
 Category: Other 
 Important:
 Subject: RE: RE: RE: IHM charge 
 Icon:  

J'ai appelé la salle de contrôle à 11h26, expliqué le fonctionnement et Hayg m'a dit que c'était bon.

Nicolas Delerue wrote:

l'obrurateur doit rester dans l'etat ou il est est. Et donc ne pas etre ouvert par l'interface s'il etait ferme avant ---> a modifier

Nicolas Delerue wrote:

Le mode de fonctionnent de l'interface a été modifié comme convenu en réunion.

Le nouveau bouton "Set dark current" effectue séquentiellement les actions suivantes:

- fermeture de l'obturateur, attente 5s et vérification

- réinitialisation des moyennes de courant

- attente 50s

- affectation des moyennes à la valeur du courant d'obscurité

- ouverture de l'obturateur, attente 5s et vérification

- réinitialisation des moyennes de courant

 

 

Entered by Super Team from 134.158.195.142 on Tue Nov 23 11:15:33 2021 wrote:

le git push de l'ihm charge a ete faite

LE SHUTTER S'OUVRE TOUT SEUL PAR L'INTERFACE. iIL DOIT ETRE OUVERT UNIQUE,ENT PAR L'UTILISATEUR ET NON PAR L'INTERFACE ---> a mofifier

 

 

 