| ID |
Date |
Author |
Status |
Type |
Category |
Important |
Subject |
Icon |
|
64
|
Mon Mar 31 15:12:59 2025 |
Entered by Hayg Guler from 134.158.205.36 on Mon Mar 31 15:12:41 2025 | New Solution | Info | DB |
|
Taurus Trend |
|
En attendant que l'archivage archive :
dans un terminal :
- inicon # ça met en place l'environment python
- cd /data/shared/commissioning_scripts/Trend_scripts/
- ./trend.sh TBT_Sum_ALL3.pck # pour avoir le trend sur tbt sum debut / milieu / fin
- ./trend.sh TBT_X_BPM4.pck # TBT X meme plage que TBT sum
- ./trend.sh TBT_Y_BPM4.pck
- ./trend.sh TBT_X_BPM5.pck
- ./trend.sh TBT_Y_BPM4.pck
- ./trend.sh RF_RPy_Trend.pck # trend des signaux RF
- Nous rajouterons ici les autres trends.
- MRSV : taurustrend obl/bpm/mrsv.01-ccd.01/fwhm_x obl/bpm/mrsv.01-ccd.01/fwhm_y
|
|
63
|
Fri Jan 10 11:11:21 2025 |
Entered by Nicolas Delerue from 134.158.195.144 on Fri Jan 10 11:11:09 2025 | | Info | Soft |
|
Saving the kickers values in recipe _LI_TL_RI | |
Someone (using the operator account) had added two incorrect lines regarding the photocathode laser in the recipe template recipe_LI_TL_RI.txt.
This was creating an error preventing from saving the kickers/septum values.
This has been fixed.
If you make changes to the recipes templates, please test them and log them!!!
|
|
62
|
Fri Jul 19 15:00:47 2024 |
Entered by Nicolas Delerue from 193.55.29.173 on Fri Jul 19 15:00:33 2024 | Fixed | Fix | Soft |
|
Jauge SF6 | |
L'affichage défectueux de la jauge SF6 a été retiré de l'IHM Gun_Section.
Un git pull a été fait. |
|
61
|
Mon Jun 10 15:03:18 2024 |
ND | Not Fixed | Problem | autre |
|
RE: Erreur dans l'IHM RF Canon+Section | |
| ND wrote: |
|
L'IHM RF Canon+Section ( RF/src/IHM_RF.py ) fait un appel (via RF/src/setup.py ) a l 'attribut LI/HFI/MAM.01/state cependant le DS LI/HFI/MAM.01 l'etat de la pression de SF6 retourne sur le panneau est donc incorrect.
|
AI1 avant purge SF6. |
| Attachment 1: Screenshot_from_2024-06-10_15-02-52.png
|
 |
|
60
|
Mon Jun 10 10:42:15 2024 |
ND | Not Fixed | Problem | autre |
|
Erreur dans l'IHM RF Canon+Section | |
L'IHM RF Canon+Section ( RF/src/IHM_RF.py ) fait un appel (via RF/src/setup.py ) a l 'attribut LI/HFI/MAM.01/state cependant le DS LI/HFI/MAM.01 l'etat de la pression de SF6 retourne sur le panneau est donc incorrect. |
|
59
|
Fri Mar 8 14:16:24 2024 |
VC | Fixed | Fix | autre |
|
Redpitaya | |
L'acquistion des redpitaya doient etre parametrée: sinon l'acquisition n'est pas à 10Hz:
les parametres redpitaya 2 et 4 sont sauvegardés par défaut
les parametres des reditaya 1 et 3 sont à vérifier
dans propriété Event
Waveform_cha et chb 0.01
dans polling
Waveform_cha et chb 50
|
|
58
|
Fri Feb 9 15:15:19 2024 |
Entered by Hayg Guler from 134.158.89.243 on Fri Feb 9 15:15:06 2024 | Under Process | Info | Tango |
|
Démarrage depuis client6 |
|
Quel Python : 2.7 dans /usr/bin
IHM :
ok, se lance, sauf erreur dans le terminal :
('------------ ', '/data/shared/Interfaces/panneaux/')
ERREUR lors de l'import IHM_health_check !!!
No module named gobject
ERREUR lors de l'import IHM_astor_server !!!
No module named gobject
('HOME_IHM = ', '/data/shared/Interfaces/panneaux/')
('IHM_SST after import #1', '15:13:53')
('IHM_SST after home IHM', '15:13:53')
('------------ ', '/data/shared/Interfaces/panneaux/')
('------------ ', '/data/shared/Interfaces/panneaux/')
ERREUR lors de l'import IHM_SST !!!
No module named gobject
Solutions ? https://stackoverflow.com/questions/37323567/install-gobject-module
Installing the system provided PyGObject:
- Open a terminal
- Execute
sudo apt install python3-gi python3-gi-cairo gir1.2-gtk-3.0
- Change the directory to where your hello.py script can be found (e.g.
cd Desktop)
- Run
python3 hello.py
Installing from PyPI with pip:
- Open a terminal and enter your virtual environment
- Execute
sudo apt install libgirepository1.0-dev gcc libcairo2-dev pkg-config python3-dev gir1.2-gtk-3.0 to install the build dependencies and GTK
- Execute
pip3 install pycairo to build and install Pycairo
- Execute
pip3 install PyGObject to build and install PyGObject
- Change the working directory to where your
hello.py script can be found
- Run
python3 hello.py
Python 3.8 :
conda /data/shared/miniconda3/envs/tango_py3.8/bin/python
Taurus : version 5.1.4
IHM se lance mais plusieurs erreur subsistent par exemple des print
(tango_py3.8) [15:24:31] operateur.thomx@client6:/tmp_mnt/data/operateur.thomx > IHM
[2] 5851
(tango_py3.8) [15:24:34] operateur.thomx@client6:/tmp_mnt/data/operateur.thomx > MainThread INFO 2024-02-09 15:24:47,654 TaurusRootLogger: Using PyQt5 (v5.12.3 with Qt 5.12.9 and Python 3.8.12)
MainThread INFO 2024-02-09 15:24:50,994 TaurusRootLogger: Plugin "taurus_pyqtgraph" lazy-loaded as "taurus.qt.qtgui.tpg"
ERREUR lors de l'import screenshot !!!
No module named 'commands'
ERREUR lors de l'import IHM_health_check !!!
cannot import name 'Qwt5' from 'taurus.external.qt' (/data/shared/miniconda3/envs/tango_py3.8/lib/python3.8/site-packages/taurus/external/qt/__init__.py)
ERREUR lors de l'import IHM_astor_server !!!
cannot import name 'Qwt5' from 'taurus.external.qt' (/data/shared/miniconda3/envs/tango_py3.8/lib/python3.8/site-packages/taurus/external/qt/__init__.py)
ERREUR lors de l'import Laser_PhotoCathode !!!
invalid syntax (astor_server.py, line 116)
ERREUR lors de l'import Modulator !!!
Missing parentheses in call to 'print'. Did you mean print("tangotest: ", val.value, " ", value0," ", value1," ",value2)? (ModulateurStatus.py, line 124)
ERREUR lors de l'import powerSupply !!!
Missing parentheses in call to 'print'. Did you mean print(exc)? (powerSupply.py, line 55)
ERREUR lors de l'import IHM_RF !!!
No module named 'PyQt4'
ERREUR lors de l'import IHMLogBook !!!
Missing parentheses in call to 'print'. Did you mean print(self.tabAttachments)? (IHMLogBook.py, line 121)
ERREUR lors de l'import DevicesController !!!
Missing parentheses in call to 'print'. Did you mean print('Error ', i)? (DevicesController.py, line 63)
ERREUR lors de l'import DevicesStatus !!!
No module named 'PyQt4'
ERREUR lors de l'import IHM_SST !!!
Missing parentheses in call to 'print'. Did you mean print(exc)? (IHM_SST.py, line 94)
ERREUR lors de l'import IHM_power !!!
Missing parentheses in call to 'print'. Did you mean print(exc)? (IHM_power.py, line 95)
MainThread WARNING 2024-02-09 15:24:55,111 TaurusRootLogger: <frozen importlib._bootstrap>:219: DeprecationWarning: taurus.qt.qtgui.plot is deprecated since 4.5. Use taurus_pyqtgraph instead
MainThread INFO 2024-02-09 15:24:57,533 TaurusRootLogger: plot: Using taurus_pyqtgraph to provide a minimal API to facilitate the transition
ERREUR lors de l'import IHM_charge !!!
No module named 'PyQt4'
ERREUR lors de l'import delays !!!
Missing parentheses in call to 'print'. Did you mean print(exc)? (delays.py, line 106)
ERREUR lors de l'import phase !!!
|
|
Draft
|
Thu Nov 2 16:27:57 2023 |
Entered by Super Team from 134.158.195.141 on Thu Nov 2 16:27:39 2023 | | Info | Tango |
|
Restauration Base de donnée TANGO | |
Restauration effectuée.
Tests en cours. |
|
56
|
Fri Sep 29 10:21:06 2023 |
Entered by Nicolas Delerue from 134.158.195.142 on Fri Sep 29 10:20:52 2023 | New Solution | Info | Docs |
|
Fonctionnement de l'interface "start ThomX for Ring" | |
L'interface de demarrage est disponible en tapant "start" dans une fenetre de ligne de commande ou dans la section anneau de PlateformeIHM.
Une copie d'ecran de la premiere page de l'interface graphique est attachée.
Chaque ligne indique une action a faire (à gauche) avec des informations à consulter (au milieu) avant de faire l 'action (à droite).
Lorsque le bouton action a ete cliqué, l'heure s'affiche ce qui permet d'etre sur que l'action a été effectuée.
Normalement en suivant l'interface ligne par ligne on effectue toutes les actions jusqu'au stockage dans l 'anneau (à condition de charger les bonnes recettes).
|
| Attachment 1: Screenshot_from_2023-09-29_10-14-23.png
|
 |
|
55
|
Thu Sep 21 12:29:54 2023 |
KD, HG | Not Fixed | Problem | Python |
|
changement paquet dans env conda | |
Bonjour à tous,
Quelqu'un ou quelques choses à changer les paquets conda dans l'environnement "#!/usr/bin/env /data/shared/miniconda3/envs/tango_py3.8/bin/python" ce qui fait planter les DS.
par exemple pour le DS TEST/ThomX_PhotoCathode, le paquet scipy.signal ne possède plus la fonction "convolv2d".
Merci de documenter les modifications que vous faites sur les environnements conda.
PS: nous avons mis à jour la version de scipy. |
|
54
|
Tue Mar 14 09:07:29 2023 |
Entered by Kevin Dupraz from 134.158.89.107 on Tue Mar 14 09:07:11 2023 | Not Fixed | Problem | Tango |
|
Erreur IHM gun section | |
Bonjour,
quand je lance l'IHM gun section, j'ai tout ces warning, cela n'empeche pas à premiere vu le fonctionnement de l'IHM mais ça peut cacher un loup plus important.
>>>>>>>>>>>>>>>>>>>>>>>>>>>
MainThread INFO 2023-03-14 09:05:48,733 TaurusRootLogger:
*********************
< Deprecation Counts (1):
1 * "format is deprecated since 4.0.4. Use format_spec or precision instead" >
MainThread WARNING 2023-03-14 09:05:53,038 srv-2.thomx.fr:20000.ER/HF/RAC.17-API.AI1.AI6: Unknown unit "▒C" (will be treated as unitless)
MainThread WARNING 2023-03-14 09:05:53,111 srv-2.thomx.fr:20000.ER/HF/RAC.17-API.AI1.AI7: Unknown unit "Mo" (will be treated as unitless)
MainThread WARNING 2023-03-14 09:05:53,283 srv-2.thomx.fr:20000.LI/OPT/OPT.02-LAS.01: Could not create HW object: device li/opt/opt.02-las.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,295 srv-2.thomx.fr:20000.LI/OPT/OPT.02-LAS.01: Could not create HW object: device li/opt/opt.02-las.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,304 srv-2.thomx.fr:20000.LI/OPT/OPT.02-LAS.01: Could not create HW object: device li/opt/opt.02-las.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,320 srv-2.thomx.fr:20000.LI/HFI/MAM.01: Could not create HW object: device li/hfi/mam.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,330 srv-2.thomx.fr:20000.LI/HFI/MAM.01: Could not create HW object: device li/hfi/mam.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,338 srv-2.thomx.fr:20000.LI/HFI/MAM.01: Could not create HW object: device li/hfi/mam.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,353 srv-2.thomx.fr:20000.LI/HFH/MAM.01: Could not create HW object: device li/hfh/mam.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,362 srv-2.thomx.fr:20000.LI/HFH/MAM.01: Could not create HW object: device li/hfh/mam.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,370 srv-2.thomx.fr:20000.LI/HFH/MAM.01: Could not create HW object: device li/hfh/mam.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,384 srv-2.thomx.fr:20000.LI/VA/AVAL.01-CMD.01: Could not create HW object: device li/va/aval.01-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,394 srv-2.thomx.fr:20000.LI/VA/AVAL.01-CMD.01: Could not create HW object: device li/va/aval.01-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,401 srv-2.thomx.fr:20000.LI/VA/AVAL.01-CMD.01: Could not create HW object: device li/va/aval.01-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,415 srv-2.thomx.fr:20000.LI/VA/AVAL.02-CMD.01: Could not create HW object: device li/va/aval.02-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,425 srv-2.thomx.fr:20000.LI/VA/AVAL.02-CMD.01: Could not create HW object: device li/va/aval.02-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,432 srv-2.thomx.fr:20000.LI/VA/AVAL.02-CMD.01: Could not create HW object: device li/va/aval.02-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,446 srv-2.thomx.fr:20000.TL/VA/AVAL.01-CMD.01: Could not create HW object: device tl/va/aval.01-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,455 srv-2.thomx.fr:20000.TL/VA/AVAL.01-CMD.01: Could not create HW object: device tl/va/aval.01-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,462 srv-2.thomx.fr:20000.TL/VA/AVAL.01-CMD.01: Could not create HW object: device tl/va/aval.01-cmd.01 not defined in the database !
MainThread WARNING 2023-03-14 09:05:53,668 srv-2.thomx.fr:20000.LI/HFI/Att.02-MOT.01.position: Unknown unit "Steps" (will be treated as unitless)
MainThread WARNING 2023-03-14 09:05:54,803 srv-2.thomx.fr:20000.LI/HFI/Dep.01-MOT.01.Position: Unknown unit "Steps" (will be treated as unitless)
MainThread WARNING 2023-03-14 09:05:55,180 srv-2.thomx.fr:20000.LI/HFI/Att.01-MOT.01.position: Unknown unit "steps" (will be treated as unitless)
<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<<
bonne journée, |
|
53
|
Thu Feb 23 12:57:41 2023 |
ND | Fixed | Info | Tango |
|
RE: Reglage alarmes temperature chiller et frigo | |
Voici les temperatures mise a jour
| ND wrote: |
|
Les couleurs des alarmes et erreur pour les chillers sont regles dans les atkpanels. Cf copies d'ecrans jointes.
Pour le chiller canon:
atkpanel CALC/ER_HF/RAC.17-API.AI1_AI2 &
Cliquer sur les points de suspension. J'ai mis comme gamme acceptable 31.6-32.4C (cf copie d'ecran).
Pour les clarinettes:
atkpanel ER/HF/RAC.17-API.AI2 &
Gamme acceptable clarinette canon: 10-35
Gamme acceptable clarinette section: 10-31
Temperature eau aimants:
atkpanel ER/HF/RAC.17-API.AI1
lignes AI6 et AI7 (pas de limites pour l 'instant)
|
|
| Attachment 1: Screenshot_from_2023-02-23_12-56-29.png
|
 |
| Attachment 2: Screenshot_from_2023-02-23_12-56-16.png
|
 |
| Attachment 3: Screenshot_from_2023-02-23_12-56-05.png
|
 |
|
52
|
Thu Feb 23 10:34:13 2023 |
ND | Fixed | Info | Tango |
|
Reglage alarmes temperature chiller et frigo | |
Les couleurs des alarmes et erreur pour les chillers sont regles dans les atkpanels. Cf copies d'ecrans jointes.
Pour le chiller canon:
atkpanel CALC/ER_HF/RAC.17-API.AI1_AI2 &
Cliquer sur les points de suspension. J'ai mis comme gamme acceptable 31.6-32.4C (cf copie d'ecran).
Pour les clarinettes:
atkpanel ER/HF/RAC.17-API.AI2 &
Gamme acceptable clarinette canon: 10-35
Gamme acceptable clarinette section: 10-31
Temperature eau aimants:
atkpanel ER/HF/RAC.17-API.AI1
lignes AI6 et AI7 (pas de limites pour l 'instant)
|
| Attachment 1: Screenshot_from_2023-02-23_10-41-14.png
|
 |
| Attachment 2: Screenshot_from_2023-02-23_10-46-01.png
|
 |
| Attachment 3: Screenshot_from_2023-02-23_10-49-52.png
|
 |
| Attachment 4: Screenshot_from_2023-02-23_10-50-54.png
|
 |
| Attachment 5: Screenshot_from_2023-02-23_10-51-11.png
|
 |
| Attachment 6: Screenshot_from_2023-02-23_10-53-08.png
|
 |
| Attachment 7: Screenshot_from_2023-02-23_10-55-49.png
|
 |
|
51
|
Thu Feb 16 18:01:13 2023 |
Entered by Nicolas Delerue from 134.158.88.175 on Thu Feb 16 17:58:07 2023 | New Solution | Info | autre |
|
Ajout temperature et resistivite de l'eau => IHM GUN_SECTION, entered from 134.158.88.175 | |
Suite à la discussion en réunion technique ce matin j'ai ajouté la temperature et la resistivite de l'eau de refroissiment des aimants dans l'IHM Gun_SECTION (je sais que ce n'est pas le bon endorit mais il n'y a pas d'IHM plus adapté).
C'est sous sortie chiller, cf copie d'écran ci-joint.
|
| Attachment 1: IHM_Gun_Section.png
|
 |
|
Draft
|
Thu Feb 16 17:58:22 2023 |
Entered by Nicolas Delerue from 134.158.88.175 on Thu Feb 16 17:58:07 2023 | New Solution | Info | autre |
|
Ajout temperature et resistivite de l'eau => IHM GUN_SECTION | |
Suite à la discussion en réunion technique ce matin j'ai ajouté la temperature et la resistivite de l'eau de refroissiment des aimants dans l'IHM Gun_SECTION (je sais que ce n'est pas le bon endorit mais il n'y a pas d'IHM plus adapté).
Cf copie d'écran ci-joint.
|
|
49
|
Tue Jan 17 11:35:09 2023 |
Entered by Nicolas Delerue from 134.158.195.142 on Tue Jan 17 11:34:54 2023 | New Solution | Info | Soft |
|
Creation automatique du repertoire avec la date | |
J'ai mis en place la creation automatique tous les matins du lundi au vendredi a 1h15 d'un repertoire avec la date dans /data/shared/Commissioning_tools/Mesure/
Apres sa creation un lien symbolique vers ce repertoire est mis sous le nom /data/shared/Commissioning_tools/Mesure/today cela permet de configurer les scripts pour qu'ils sauvent dans /data/shared/Commissioning_tools/Mesure/today
Me prevenir si cela ne fonctionne pas.
|
|
48
|
Thu Dec 15 12:10:32 2022 |
Entered by Nicolas Delerue from 134.158.88.175 on Thu Dec 15 12:10:17 2022 | New Solution | Info | autre |
|
IHM recette | |
J'ai supprimé l'erreur affichée par l'IHM recettes quand l'état du DS est ON... Donc normalement les erreurs affichées maintenant devraient être pertinentes.
J'ai monté le nombre d'erreurs affichées à 10.
Me dire si il y a d'autres erreurs à masquer.
|
|
47
|
Mon Nov 7 23:47:16 2022 |
ND | New Solution | Info | Tango |
|
RE: Arrêt Machine | |
Je l'ai ajouté dans PlateformeIHM, section Outils et j'ai fait un git pull.
| Entered by Kevin Dupraz from 134.158.89.107 on Fri Nov 4 18:56:54 2022 wrote: |
|
Bonjour,
Une commande "STOP_THOMX" a été ajouté au DS script de ThomX : "TEST/HL/ThomX_Script".
Cette commande permet d'arrêter toute la machine en une fois (Alimentation + éléments pulsés + chillers/frigo + modulateur + Laser).
*!* Une confirmation est demandé avant l'arrêt. Il faut mettre "true" pour confirmer l'arrêt. *!*
L'info final donne les DS qui ne sont pas éteints. Souvent le modulateur qui prend du temps pour se mettre en off.
Pensez à tourner la clé PA en partant.
|
|
|
46
|
Mon Nov 7 22:34:11 2022 |
Entered by Nicolas Delerue from 80.119.21.73 on Mon Nov 7 22:33:55 2022 | New Solution | Info | Soft |
|
Scan phase section | |
J'ai ajouté dans plateforme IHM un bouton "scan RF phase" qui scan la phase RF section entre 105 et 125 degrees pour trouver le meximum d'energie et la FWHM minimum du faisceau sur TL/SST2.
Pour l'instant il n'y a pas d'interface à part le plot qui s'affiche à la fin mais j'en ajouetrai une prochainement.
|
|
45
|
Fri Nov 4 18:57:10 2022 |
Entered by Kevin Dupraz from 134.158.89.107 on Fri Nov 4 18:56:54 2022 | New Solution | Info | Tango |
|
Arrêt Machine | |
Bonjour,
Une commande "STOP_THOMX" a été ajouté au DS script de ThomX : "TEST/HL/ThomX_Script".
Cette commande permet d'arrêter toute la machine en une fois (Alimentation + éléments pulsés + chillers/frigo + modulateur + Laser).
*!* Une confirmation est demandé avant l'arrêt. Il faut mettre "true" pour confirmer l'arrêt. *!*
L'info final donne les DS qui ne sont pas éteints. Souvent le modulateur qui prend du temps pour se mettre en off.
Pensez à tourner la clé PA en partant. |