Entry   ND; Test cyclage aimants 
    Reply   IC; RE: Test cyclage aimants cylage_quad8A.png
Message ID: 669     Entry time: Wed Jan 18 14:02:39 2023     In reply to: 668
 Author: IC 
 Status: Under Process 
 Type: Anneau 
 Category: Aimants 
 Important:
 Subject: RE: Test cyclage aimants 
 Icon:  

I have decresed the Imax to 8 A and loaded the new cycling curves

RI-C1/PS/QP.06 and RI-C2/PS/QP.02: normally cycling  with Imax 8 A , finish without error => PS to be checked for Imax >8 A (nominal 10 A

ND wrote:

17h25: Test de cyclage de

RI-C1/PS/QP.05

RI-C1/PS/QP.06

RI-C2/PS/QP.02

 

Resultats

RI-C1/PS/QP.05

RI-C1/PS/QP.06: Failed at 11% when magnet reached 10A => Ne pas cycler au dela de 9.4A

RI-C2/PS/QP.02: Failed at 11% when magnet reached 10A=> Ne pas cycler au dela de 8.5A

 

Attachment 1: cylage_quad8A.png  22 kB  | Hide | Hide all
cylage_quad8A.png