Message ID: 2     Entry time: Tue Oct 1 12:24:11 2019     In reply to: 1
 Author: Ronic Chiche 
 Status: Fixed 
 Type: issue 
 Category: utilities 
 Location: Optical room 
 Title: Chiller of the new laser amplifier  

Today, the chiller worked at 17°C during 3 hours without error, no freezing nor flow sensor error.

Ronic Chiche wrote:

We observed 2 issues for the chiller of the new CELIA laser amplifier:

  • setting the water temperature to 17°C, the chiller water turns to ice close to the water filling port !!! => temperature too low ?
  • even when the water is fluid, one has a flow sensor error ! => pump charge too strong ? => reduce the water pipe length.

We have set the water temperature to 20°C and we shortened the water pipes by 2-3m

         => both problems seem to be fixed.

Now, we can try to reduce the setting temperature.

 