HOME SBOX THOMX MINICAV Utilities
THOMX orders THOMX installation THOMX commissioning THOMX control command
  Status of installation, including shipping and de-installation of test setups.  Not logged in ELOG logo
Entry   Chiller of the new laser amplifier , posted by Ronic Chiche at Optical room about utilities 
    Reply   Chiller of the new laser amplifier , posted by Ronic Chiche at Optical room about utilities 
Message ID: 1     Entry time: Mon Sep 30 16:32:31 2019     Reply to this: 2
 Author: Ronic Chiche 
 Status: Fixed 
 Type: issue 
 Category: utilities 
 Location: Optical room 
 Title: Chiller of the new laser amplifier  

We observed 2 issues for the chiller of the new CELIA laser amplifier:

  • setting the water temperature to 17°C, the chiller water turns to ice close to the water filling port !!! => temperature too low ?
  • even when the water is fluid, one has a flow sensor error ! => pump charge too strong ? => reduce the water pipe length.

We have set the water temperature to 20°C and we shortened the water pipes by 2-3m

         => both problems seem to be fixed.

Now, we can try to reduce the setting temperature.

ELOG V3.1.4-395e101