Entry   Airflow installation, posted by Ronic Chiche at ThomX igloo about mechanics 
    Reply   Airflow installation, posted by Ronic Chiche at ThomX igloo about mechanics 
Message ID: 15     Entry time: Thu Jun 10 17:45:09 2021     In reply to: 14
 Author: Ronic Chiche 
 Status: Fixed 
 Type: info 
 Category: mechanics 
 Location: ThomX igloo 
 Title: Airflow installation 

The AC plug and the power cord of the airflow were quite hot because they have been dimensioned for 16A current and the total current is above.
AirC2 company should replace them with 32A equipment (6mm2 power cord + 32A Hypra AC plug) in the next days.
 

Ronic Chiche wrote:

On the 27th of May, the Airflow has been dismounted from the optical room to be mounted around the optical cavity by the AirC2 company.

here is email from Yann :

Le flux est rentré dans la casemate.
Lundi la société AirC2 revient pour installer les rideaux.
Petits couacs :
- 2 plaques de faux plancher à découper
- le saut de loup à été déplacé (à voir si c'est OK pour tout le monde)
- filet de toit à retendre
- poutres du toit à remettre
- main courante du faux plancher à retirer
- attention au coin du flux au niveau du saut de loup (à baliser et protéger)

 

ELOG V3.1.4-395e101