HOME SBOX THOMX MINICAV Utilities
SBOX orders SBOX installation SBOX commissioning SBOX control command
  Status of commissioning, report also here plots are reports.  Not logged in ELOG logo
Entry   chiller for CELIA amplifier, posted by Aurélien Martens at Optical room about utilities 
    Reply   chiller for CELIA amplifier, posted by Aurélien Martens at Optical room about utilities 
Message ID: 121     Entry time: Thu Jul 28 13:52:23 2022     Reply to this: 122
 Author: Aurélien Martens 
 Status: Fixed 
 Type: report 
 Category: utilities 
 Location: Optical room 
 Title: chiller for CELIA amplifier 

The chiller of CELIA amplifier has been moved from the corridor to the changing room in front of PLIC. 

It was not functionning well (quick drop of flow below 0.9l/min). After several cleanings of the filter, shorting the water circuit a stable 2.1l/min flow was obtained. Then the water circuit was elongated to go close to the amplifier but not into it. Allowing to get about 1.3l/min stable. Now the amplifier is conencted, the filter has been cleaned again twice and the flow seem stable with 1.4l/min. New filters have been ordered and must arrive quickly. Changing it is necessary I think. 